A cabinet fan rated at 100 m³/h in free air may deliver less with a filter. Compare the operating point using the resistance of the complete airflow path.
Free-air flow is measured with little resistance to airflow. A control cabinet introduces a filter, outlet and internal obstructions that affect the air the assembly can actually move.
Describe the complete ventilation path
List the fan-filter unit, outlet filter, cutouts and required enclosure protection. Give the expected heat load and ambient conditions where available. Ask for an operating point that accounts for the resistance of the selected combination.
A fan advertised at 100 cubic metres per hour
Its 100 m³/h free-air figure does not establish that the assembled cabinet receives that flow. Two fans with similar headline ratings may deliver different airflow against the same filter resistance.
Enquiry checklist
| Item | What to record |
|---|---|
| Thermal duty | Heat load and surrounding temperature. |
| Air path | Inlet and outlet combination. |
| Fit | Cutout, voltage and protection requirements. |
Check the quotation Add a second view from inside the closed cabinet. Mark the space taken up by connectors, wiring or rear accessories so the footprint on the front panel is only one of the dimensions compared.
Request performance information for the proposed assembly. Include the replacement filter mat in the spare parts quotation.
Sample enquiry to ISATIS
Please quote the fan and matching outlet filter. Give the expected installed airflow, assumptions and replacement filter code.