Check both the cutout and scaling of a panel meter. Use a 12 mA midpoint to verify a linear 4–20 mA input mapped to a 0–10 bar display.
A door-mounted meter must fit the opening and connect correctly to the signal loop. A display range in bar says little about the electrical input or how the instrument is powered.
Read the mechanical and signal records
Record cutout, door thickness, depth, signal type and auxiliary supply if present. Distinguish a loop-powered indicator from an externally powered unit. Include the intended lower and upper display values and decimal position.
Checking a 4–20 mA scale
With a linear 4–20 mA input mapped to 0–10 bar, 12 mA corresponds to 5 bar. This midpoint provides a simple cross-check for the proposed scale and the display format.
Enquiry checklist
| Item | What to record |
|---|---|
| Door | Cutout and usable depth. |
| Loop | Input signal and power arrangement. |
| Display | Units, range and resolution. |
Check the quotation Add a second view from inside the closed cabinet. Mark the space taken up by connectors, wiring or rear accessories so the footprint on the front panel is only one of the dimensions compared.
Ask whether scaling is configured before delivery or set during commissioning. Include any alarm outputs in the scope if the existing panel uses them.
Sample enquiry to ISATIS
Please quote an indicator for the attached loop and cutout. State its power arrangement and confirm the display at the lower, midpoint and upper input values.