Gauge, absolute or differential; how range and turndown affect accuracy; which wetted materials suit which service; and when remote seals beat impulse lines.
Pressure transmitters are the most common instruments in a process plant. They measure line and vessel pressure, infer level and flow from differential pressure, and feed many of the trips in the safety system. Because they are so familiar, they are often specified by copying the last data sheet, and that is where avoidable errors start: the wrong range, a diaphragm that corrodes, a remote seal that drifts with the weather or an impulse line that freezes in winter.
This guide walks through the choices that decide whether a pressure transmitter gives a reliable reading for its whole service life.
Gauge, absolute or differential
- Gauge pressure is measured against the atmosphere and suits most line and vessel pressures well above atmospheric.
- Absolute pressure is measured against a vacuum. It is needed for vacuum service, for low pressures where changes in barometric pressure would matter, and for gas flow and density calculations.
- Differential pressure (DP) is the difference between two process connections. It is used for flow across orifice plates and other primary elements, for level in closed vessels and for filter and strainer monitoring.
For DP service, check the static pressure rating as well as the range. A transmitter measuring a few hundred millibar across an orifice in a 100 bar line must withstand the full line pressure on one side during start-up or if an impulse line is isolated.
Range, turndown and accuracy
Modern transmitters can be ranged down a long way from their upper sensor limit, but accuracy is stated at a reference range and gets worse as the span is reduced. Choose the sensor range so that the calibrated span sits in its better region, rather than relying on a large turndown. The total probable error, combining reference accuracy, ambient temperature effect, static pressure effect and long-term stability, is a better basis for comparison than the headline accuracy figure. For a flow loop based on DP, remember that flow varies with the square root of DP, so the lower part of the flow range uses a very small part of the DP range.
Materials and wetted parts
| Wetted material | Typical use | Watch out for |
|---|---|---|
| 316L stainless steel | General hydrocarbon, water and utility service | Chlorides, and pitting in seawater or brine |
| Alloy C-276 (Hastelloy) | Chlorides, sour service, many acids | Higher cost; check compatibility with oxidising acids |
| Monel 400 | Hydrofluoric acid, seawater | Not suitable for oxidising media |
| Tantalum | Hot hydrochloric and sulphuric acid | Expensive; thin diaphragms are easily damaged |
| Gold-plated diaphragm | Hydrogen service | Hydrogen permeates thin metal diaphragms and causes drift without it |
For sour service, wetted parts and bolting should conform to NACE MR0175 / ISO 15156. Fill fluid matters too: silicone oil is the default, but oxygen and chlorine service need an inert fill, and food or pharmaceutical service may need an approved fill.
Impulse lines or remote seals
Impulse lines are simple and cheap, but they plug, freeze, collect gas or condensate and leak. Close coupling the transmitter to the process, sloping the lines correctly and heat tracing them where needed solves most problems. Remote diaphragm seals remove the impulse lines altogether and are the usual answer for viscous, crystallising, corrosive or very hot fluids. The price is a temperature error from the fill fluid in the capillary and a slower response. Keep capillaries short and equal on both sides, mount the transmitter below the lower tap for vacuum service and consider a direct-mount seal on one side to reduce the error.
Installation rules that save trouble
- For liquid service, mount the transmitter below the tapping so that gas drains back to the process; for gas service, mount it above so that liquid drains away.
- Use a manifold that allows isolation, equalisation and venting for calibration without disturbing the process.
- On steam, keep the condensate legs full and equal, and never let live steam reach the sensor.
- Avoid pressure pulsation and vibration at the mounting point, or add a snubber or remote mounting where they cannot be avoided.
Electronics, diagnostics and certification
A 4-20 mA signal with HART remains the norm, with Foundation Fieldbus or PROFIBUS PA on some projects and wireless transmitters where cabling is expensive. Useful diagnostics include plugged impulse line detection and sensor health checks. The hazardous area certification (Ex d or Ex ia under ATEX or IECEx) must match the zone and the loop design. A transmitter used in a safety function should have a SIL capability certificate or proven-in-use data so that it can be included in the SIL verification.
Frequently asked questions
How often should a pressure transmitter be calibrated?
There is no single interval. Modern transmitters are very stable, and many plants check them every two to four years, with shorter intervals for custody transfer, safety functions and severe service. Historical as-found results are the best guide to adjusting the interval.
Why does a DP transmitter read differently after a hot day?
Usually because of remote seals: the fill fluid in the capillaries expands with temperature and changes the reading, especially with long or unequal capillaries. Unequal impulse line temperatures and partly empty wet legs are other common causes.