Two assemblies can have the same four-metre capillary and different zero offsets. See how to mark the instrument elevation and capillary route on a seal enquiry.
Send two dimensions with a remote-seal enquiry: the capillary length along its route and the vertical distance between the diaphragm centre and the pressure instrument. Identical flanges do not mean two assemblies will behave alike on site.
Draw the route and mark the two elevations
The fill fluid in the capillary forms a liquid column. Its head can affect the reading, while the length of the run and the temperatures along it matter to response. A sketch showing the instrument, seal and exposed sections tells the reviewer more than a request for a “long capillary.”
Two installations, both with four metres of capillary
In one installation the gauge is level with the diaphragm. In the other it sits two metres above it. The four-metre dimension helps specify the tubing in both cases, but it does not establish the zero correction for the second installation.
Enquiry checklist
| Item | What to record |
|---|---|
| Elevation datum | Mark the diaphragm centre and the instrument on the same drawing. |
| Route | Show the required length and any hot or cold sections. |
| Process connection | State the flange size, rating and facing from the line specification. |
Check the quotation On the quotation drawing, mark the connection on each side and identify which seals or adapters come with the assembly. This makes two offers with the same instrument range comparable.
Ask for the proposed fill fluid, elevation basis and operating temperatures. An existing filled assembly can be identified without separating its components.
Sample enquiry to ISATIS
Please quote the seal and instrument as an assembly for the attached installation. The drawing gives the capillary route and vertical offset separately. Identify the process connection, fill fluid and temperature limits used in your selection.