Is 0.2 bar absolute or gauge pressure? Work through the conversion at a stated atmospheric pressure and specify the correct reference for a vacuum gauge.
“0–2 bar” tells the buyer the scale endpoints but not what zero represents. Determine whether the process needs pressure relative to atmosphere or to absolute vacuum before selecting the transmitter.
Reconcile the process documents
Look for the reference on the instrument datasheet, loop record and process drawing. Write bar(a) or bar(g) explicitly where applicable. If the documents disagree, changing the unit label in the purchase sheet does not resolve the engineering question; the process owner must establish the intended reference.
The same number can describe very different conditions
With atmospheric pressure taken as exactly 1 bar for illustration, 0.2 bar absolute is approximately −0.8 bar gauge. An enquiry that says only “0.2 bar” loses this distinction. Use actual local atmospheric pressure when a real conversion calls for it.
Enquiry checklist
| Item | What to record |
|---|---|
| Measurement point | Tag and service description. |
| Reference | Absolute, gauge or differential, with explicit units. |
| Output scaling | Process values assigned to the low and high output endpoints. |
Check the quotation Keep the process pressure, the instrument range and the point of interest in separate fields. Ask for the offered values alongside yours, with the unit and pressure reference written out.
Ask for the sensor type and configured range alongside the order code. A matching pair of numbers in a catalogue does not establish the pressure reference.
Sample enquiry to ISATIS
Please quote against the pressure reference on the attached datasheet. State the sensor type, both calibrated endpoints and their complete units in the offer.