Choosing a differential-pressure gauge for a filter? Compare the differential range with the permitted static line pressure and specify both in the enquiry.
A filter gauge measures the difference between its ports, but its body and connections also see the pressure in the line. A differential range on its own does not specify a suitable instrument.
Start with what the operator needs to read
Request the clean-filter pressure drop and the terminal drop used for replacement, with units and fluid identification. Then obtain the pressure on each side relative to ambient. This is particularly important when a gauge familiar from an air duct is proposed for a pressurised liquid line.
Small differential, substantial line pressure
At 8 bar upstream and 7.9 bar downstream, the differential is 0.1 bar. That does not make this a low-static-pressure application. The wetted components still have to suit the line, and the proposed model needs an appropriate documented pressure rating.
Enquiry checklist
| Item | What to record |
|---|---|
| Differential | Give clean and terminal pressure drops in the same units. |
| Line pressure | Record operating and maximum design conditions. |
| Application | Identify fluid, wetted materials and any alarm-contact requirement. |
Check the quotation Keep the process pressure, the instrument range and the point of interest in separate fields. Ask for the offered values alongside yours, with the unit and pressure reference written out.
Use a unit in each comparison column. In this example the differential is 100 mbar. A quote may give the scale in mbar and the allowable line pressure in bar. Compare each figure with its own requirement.
Compare display range and permitted static pressure in separate columns. If only local indication is needed, price the switch option separately.
Sample enquiry to ISATIS
Please quote a filter differential-pressure gauge for the stated fluid and clean and terminal drops. Confirm the display range, permissible pressure at each port and wetted materials.