Use a rising-pressure example to distinguish the adjustable range, operating point, reset point and deadband on a pressure switch quotation.

A request for a six-bar pressure switch leaves several questions open. Six bar might mean the normal line pressure, the switch point or the upper limit of the adjustment range. Define the required change of contact state and the direction from which the process reaches it.

Put actuation and reset on separate lines

Suppose the contacts must change state as gauge pressure rises to 6 bar and return as it falls to 5.5 bar. The difference is 0.5 bar. This is the deadband for that illustrative cycle. A switch intended to act on falling pressure needs the opposite direction stated explicitly.

What the adjustable range tells you

A quotation stating an adjustable range of 0 to 10 bar does not establish the reset behaviour. Ask for the specified deadband or adjustment range for it, any tolerance applicable to the setpoint, and the conditions under which the figures apply. Keep allowable process pressure in a separate field.

Check What to record
Enquiry reference
Direction in this example Rising pressure
Actuation 6 bar gauge
Reset 5.5 bar gauge
Deadband 0.5 bar

Check the quotation Keep the process pressure, the instrument range and the point of interest in separate fields. Ask for the offered values alongside yours, with the unit and pressure reference written out.

Match the electrical and process interfaces

Provide the contact arrangement and rating required by the circuit, the process fluid and connection, and enclosure requirements. For classified service, give the approved project requirements and obtain a review of the exact proposed marking and certification.

Write a comparable enquiry

For the example, request actuation at 6 bar gauge on a rising pressure and reset at 5.5 bar gauge on a falling pressure, with tolerances per the attached data sheet. Require both values in the quotation. Actual trip values must come from the approved process documentation.