ISATIS GROUP Arikeh Sanat IsatisInstrumentation · Control · Safety

Electrical, power & Ex

ComAp equipment, sourced and integrated

ComAp is a Czech company from Prague that designs controllers for generator sets, engines, paralleling and microgrids. It was founded in 1991, and its InteliGen controller of 2000 became a reference in the diesel genset market.

ComAp logo
Czech Republic/Since 1991
Country
Czech Republic
Founded
1991
Known for
Generator set controllers

Related services

Related engineering guide

How to Read an Instrument Order Code Before Requesting a Spare

Read the guide

Have a part number?

Send the part number or datasheet and we reply with availability, lead time and price.

Send an enquiry

ComAp was founded in 1991 by three friends in a one-room office in Prague, and its first contract was for voice annunciators on the Prague Metro. The name is short for Computer Application. In 2000 the company released InteliGen, presented as the first all-in-one generator controller, followed in 2002 by InteliLite for single gensets and InteliSys for CHP and large engine applications. The first foreign subsidiary opened in Bristol, UK, in 2001, and ComAp now lists 18 subsidiaries. Later milestones include the InteliVision display family, the WebSupervisor remote monitoring platform in 2010, InteliDrive controllers for engines and marine use, InteliNeo controllers for microgrids and battery storage, and InteliGen 1000 for paralleling in 2022. Mains and bus tie controllers are covered by the InteliMains family, such as InteliMains 210 and 1010.

Many ComAp controllers installed in Iran belong to the older NT generation, such as InteliLite NT AMF 25, InteliCompact NT and InteliGen NT. Several of these are discontinued: InteliLite AMF25 is replaced by InteliLite 4 AMF 25, and InteliGen 500 G2 succeeds both InteliGen 500 and the InteliGen NT GC line. A successor is not always a drop-in part, so before replacement we compare the terminal layout, the number of binary and analog inputs and outputs, the CAN or J1939 interface to the engine ECU, the communication modules fitted and the cut-out size in the panel door. The archive file from the old controller, read with the configuration tool (InteliConfig for current models), holds the protections, set points and logic, and should be saved before the old unit is removed so the new one can be set up the same way.

We supply ComAp controllers, displays, extension modules and communication plug-in modules for genset packagers, data centre and hospital standby systems, and plants running gas engines or paralleled diesel gensets. The order starts from the exact model and part number on the controller label, the firmware version where available, and the single line diagram of the paralleling scheme. For a migration from an NT unit to a current model, we list the hardware differences and the wiring changes at the quotation stage. Spare displays and modules are matched to the controller generation, since NT and current models use different accessories.

Electrical enclosures and cable entries
Electrical enclosures and cable entries · ISATIS editorial illustration

ComAp product families we supply

  • 01InteliLitesingle genset controllers, such as InteliLite 4 AMF 25
  • 02InteliGenparalleling controllers, such as InteliGen 500 G2 and 1000
  • 03InteliSyscontrollers for CHP and large engines
  • 04InteliMainsmains and bus tie controllers
  • 05InteliDriveengine and marine controllers
  • 06InteliVision displays and WebSupervisor remote monitoring
  • 07InteliNeomicrogrid and battery storage controllers

Typical applications

  • 1Standby and prime power diesel gensets
  • 2Paralleling of multiple gensets with the grid
  • 3Gas engine CHP plants
  • 4Hybrid microgrids with solar and battery storage

FAQ

Common questions about ComAp.

My InteliLite NT AMF 25 failed. What replaces it?

ComAp lists InteliLite 4 AMF 25 as the successor. Before ordering, compare the terminals, inputs and outputs, ECU interface and panel cut-out, and keep the archive file of the old unit to rebuild the settings.

What is the difference between InteliLite and InteliGen?

InteliLite controls a single genset, typically with automatic mains failure start. InteliGen is built for paralleling several gensets with each other or with the grid, with load sharing and synchronising functions.

What do you need to quote a ComAp controller?

The model and part number from the controller label, the firmware version, the engine type and ECU, and a photo of the rear terminals. For paralleling systems, the single line diagram is also needed.

Electrical, power & Ex

Other brands in this discipline.

All brands
  • APC logo
  • Eaton logo
  • Lovato Electric logo
  • Mean Well logo
  • Cortem logo
  • BARTEC logo
  • R. STAHL logo
  • MEDC logo
  • Hawke International logo
  • Pfannenberg logo
  • Itelcond logo
  • Rittal logo
  • WAGO logo

Send us your datasheets, P&IDs or tender documents.

We review them and reply with a technical and commercial proposal.