Will a solenoid valve open when both sides start near 2 bar? Check the minimum available differential at startup as well as the valve’s maximum pressure rating.
The maximum pressure on the valve label does not establish operation at low differential pressure. Record conditions on both sides, particularly at start-up.
Line pressure is not pressure drop
Some servo-assisted or pilot-operated designs depend on differential pressure. Compare datasheets for the precise order codes. Fluid, orifice and flow direction also matter, and none of these can be inferred from coil voltage.
A vessel with equal pressure on both sides
If both ports are at approximately 2 bar when the equipment starts, the valve does not have 2 bar of differential pressure available. Ask the process owner for start-up, normal running and shutdown conditions separately.
Enquiry checklist
| Item | What to record |
|---|---|
| Pressures | Minimum and maximum inlet and outlet conditions. |
| Function | Normal state and required flow paths. |
| Coil | Voltage, current type and electrical connection. |
Check the quotation Ask for the offered valve symbol and full order code beside the installed one. If a coil, connector or sub-base is priced separately, list it as a separate quotation line.
Enter a minimum permissible differential in the comparison only when supported by the proposed model’s documentation. Resolve an unknown before issuing the order.
Sample enquiry to ISATIS
Please quote for the three operating states listed. Confirm the operating principle and minimum differential pressure required for this specific valve.