Convert 10 pulses per litre into litres per pulse and check the result against a 500-pulse total. A worked example for specifying a replacement flow totalizer.
Write the direction of the pulse factor explicitly. Ten pulses per litre and ten litres per pulse use the same numbers for opposite conversions.
Check the transmitter and the counter as one interface
Get the meter’s actual output type, signal level and maximum frequency. Compare these with the counter input and counting capacity. A photograph of the sensor marking or certificate preserves the units more reliably than copying the number alone.
A 500-pulse acceptance example
At 10 pulses per litre, 500 pulses represent 50 litres. If the counter treats the setting as 10 litres per pulse, it displays 5,000 litres instead. Including a simple worked point gives purchasing and instrumentation a clear common check.
Enquiry checklist
| Item | What to record |
|---|---|
| Factor | Value with numerator and denominator units. |
| Input | Signal type and counting capability. |
| Display | Totalised volume unit, decimal places and repeat-output requirement. |
Check the quotation Copy a complete indication from the old scale or configuration screen, including its unit. Use that example to ask how the same flow would be represented on the proposed unit.
Copy the units shown by the old totalizer. If the replacement accepts litres per pulse, an existing value of 10 pulses per litre becomes 0.1 litre per pulse. Put both equivalent values on the order sheet.
Include a sample pulse count and expected total in the acceptance record. It catches a units error without substituting for calibration or a functional test.
Sample enquiry to ISATIS
Please quote a totalizer for the existing meter output. The attached sheet gives the original pulse-factor units. Confirm input frequency range and the intended totalised display unit.