Are two 10 A supplies redundant for a 15 A load? Calculate what must remain powered after one failure and compare it with the surviving supply’s rating.
Parallel operation can increase available current. Redundancy also requires the surviving supply path to carry the specified essential load when another path becomes unavailable.
Define the single-failure condition
List essential load, peak current, ambient derating and the redundancy or decoupling hardware. Check the capacity of each remaining path under the stated condition and identify how loss of a supply is signalled.
Two 10 A supplies feeding 15 A
Together the units may cover a 15 A load in normal operation. With one 10 A unit remaining, they do not provide full-load redundancy at 15 A. Identify any load shedding explicitly if it forms part of the design.
Enquiry checklist
| Item | What to record |
|---|---|
| Load | Essential continuous and peak currents. |
| Surviving path | Rating after one supply is lost. |
| Supervision | Decoupling and failure indication. |
Check the quotation State the load during normal operation and during the most demanding part of the duty cycle separately. Ask which of these conditions determines the offered rating.
Total the loads that must remain energized after a failure. In the 15 A example, if the design permits shedding 6 A, the surviving supply must support 9 A. Compare that with the supply’s usable rating at the actual cabinet temperature.
Have the bidder state the supported load after a single failure. Quote the required redundancy module and alarms with the supplies.