Prepare a steam-trap replacement enquiry with the equipment duty, working differential pressure, load and connection details.
Two traps can fit the same pipe and serve different duties. A trap draining a distribution main and one serving a modulating heat exchanger may see very different loads and back pressures. Identify the equipment being drained before asking for a replacement.
Identify the duty
Record the equipment tag, existing trap model and orientation. Indicate whether the request covers a complete trap, an internal kit or a connector-mounted unit. A photograph of the complete installation can establish the scope more clearly than a cropped casting mark.
Describe pressure on both sides
Give the upstream working pressure and the downstream condensate-return pressure, with units. If the figures vary with load, record the range. A site steam header rating alone cannot describe the differential pressure available at the trap.
| Check | What to record |
|---|---|
| Service | Equipment tag and duty |
| Operating point | Upstream and return pressure, units and load |
| Scope | Complete trap, connector or specified parts |
Check the quotation Distinguish a replacement for the installed body from a complete replacement station. Mark the flow direction and the components that stay on the line so the scope can be priced consistently.
Separate running load from startup
Include the normal condensate load and any separately established warm-up load. Label estimates as estimates. Ask the supplier to identify the selection point on the proposed capacity curve so the engineer can review the basis.
Compare the offers
Check the connection standard, face-to-face length, flow direction, serviceable parts and delivery scope. If either the trap family or arrangement changes, send the comparison to the plant engineer for review before placing the order.
Related equipment and quotations
Spirax Sarco equipment guide · Prepare an enquiry for ISATIS