A four-core cable may have a spare conductor. Match the Pt100 wiring arrangement to the input card and distinguish connected sensor leads from unused cores.
A Pt100 designation and temperature range do not fully specify a replacement. Record the actual two-, three- or four-wire sensor connection and the input that reads it.
Trace the signal as far as the receiver
If there is a head-mounted transmitter, the cable back to the control room may carry current. Its core count does not identify the element wiring inside the head. A terminal photograph, transmitter input specification and approved loop drawing provide a clearer basis for selection.
Four cable cores do not always mean a four-wire element
An installation may use a four-core cable with one spare. Counting cores alone would suggest the wrong sensor termination. Record the conductors actually connected at the element and the receiver.
Enquiry checklist
| Item | What to record |
|---|---|
| Element | Type, number of elements and required tolerance class. |
| Wiring | Actual element connection and supported receiver input. |
| Mounting | Sheath diameter, insertion length and mechanical connection. |
Check the quotation Draw the temperature loop from sensing element to receiving input. Circle the part being purchased and mark the items that will stay in service, including any existing cable.
Ask for three explicit confirmations: element type, wire arrangement and interface to the existing receiver. The phrase “Pt100 compatible” does not answer all three.
Sample enquiry to ISATIS
Please quote a replacement sensing element for the existing head and transmitter. Confirm the element and lead arrangement against the attached drawing. The transmitter output cable is outside the supply scope.