Sensor technologies, detector placement, alarm set points, voting and testing for fixed gas detection on oil, gas and petrochemical sites.
A fixed gas detection system has one job: to notice a hazardous release early enough for people to leave and for the plant to act before the gas finds an ignition source or a person. Most systems that fail in that job do not fail because a detector broke. They fail because the wrong sensor was chosen for the gas, the detector was mounted where the gas never goes, or nobody checked that it still responds.
This guide walks through the decisions that matter on oil, gas and petrochemical sites: sensor technology, placement, alarm levels and voting, and the testing that keeps the system honest.
Start with the hazard, not the catalogue
Every detector selection begins with three questions: which gases can be released, at what pressure and temperature, and what the detection is supposed to trigger. A detector meant only to warn operators in a compressor house can be chosen differently from one that trips an emergency shutdown valve. List the release sources from the P&IDs and the hazardous area classification, note the gas properties for each, and decide for each area whether detection leads to an alarm, to ventilation or to an executive action.
Sensor technologies compared
| Technology | Detects | Strengths | Watch out for |
|---|---|---|---|
| Catalytic bead (pellistor) | Most flammable gases and vapours, including hydrogen | Simple, low cost, responds to almost any combustible | Poisoned by silicones and lead, inhibited by H2S; needs oxygen; can fail without showing a fault |
| Point infrared (NDIR) | Hydrocarbons | No poisoning, works in inert atmospheres, fail-safe self-diagnostics, long life | Cannot see hydrogen; reading depends on the calibration gas |
| Open-path infrared | Hydrocarbon clouds along a beam of several tens to a couple of hundred metres | Covers a line, not a point; good along process boundaries and pipe racks | Measures LEL·metres, not concentration; needs alignment and a clear line of sight |
| Electrochemical | Toxic gases (H2S, CO, SO2, Cl2) and oxygen | Accurate at ppm level, low power | Limited life, typically two to three years; sensitive to heat and very dry air; cross-sensitivities |
| Semiconductor (MOS) | H2S | Tolerates hot, dry climates better than electrochemical cells | Can lose sensitivity after long periods without gas; needs regular bump testing |
| Ultrasonic leak detection | The sound of pressurised gas escaping | Responds regardless of wind direction and gas cloud position | Says nothing about concentration; only works for releases above a few bar; background noise must be mapped |
In practice many sites combine technologies: point infrared detectors near specific sources, open-path detectors along the boundary of a process area, electrochemical or MOS detectors for H2S, and ultrasonic detectors on high-pressure gas equipment in open, windy areas.
Where to mount a detector
The old rule says methane rises, so detectors go high, while propane and H2S are heavier than air, so detectors go low. The rule is a starting point, not a design. A high-pressure jet release behaves according to its momentum, not its density, cold gas from a flashing liquid sinks even if the gas itself is light, and wind and ventilation in an open module move a cloud far more than buoyancy does.
Two approaches are used to decide coverage:
- Prescriptive: detectors at fixed spacing around each source, following company or industry rules. Simple to apply and audit, but it can leave gaps or put detectors where they add little.
- Performance-based gas mapping: release scenarios are modelled and detectors are placed to reach a target coverage, as described in ISA TR84.00.07. It costs more engineering time but shows how much of the hazard the system actually sees.
Whichever method is used, the result should be checked on site: a detector behind a cable tray, or in a corner the airflow never reaches, is not the detector that was on the drawing.
Alarm levels and voting
Flammable gas detectors usually have two set points, commonly around 20% LEL for the first alarm and 40% to 60% LEL for the high alarm. Toxic set points come from the site philosophy and occupational exposure limits; for H2S, low single-digit and around 10 ppm set points are typical. The values must be written into the cause and effect matrix together with the action each one triggers.
When detection initiates an executive action such as isolation, depressurisation or shutting down ventilation, a single detector should not normally trip the plant. Voting such as 2ooN, two confirmed detections out of a group covering the same area, avoids spurious trips from one faulty or contaminated head. Faulty or inhibited detectors must be handled explicitly in the voting logic, and the function as a whole is then designed and verified as a safety instrumented function under IEC 61511.
Signals, diagnostics and certification
Most fixed detectors provide a 4–20 mA output, often with HART, where currents below 4 mA indicate fault, inhibit or beam block. The fire and gas controller must distinguish these states from a real zero reading. Detectors for flammable gases should have performance approval to IEC 60079-29-1 and hazardous area certification (ATEX or IECEx) for the zone; detectors used in safety functions should come with a SIL capability statement and the failure data the SIL verification needs.
Testing and calibration in practice
- Bump test: a short exposure to gas that proves the detector responds and the alarm reaches the control room. It should be done far more often than full calibration, especially for electrochemical and MOS sensors.
- Calibration: zero and span with certified gas, recorded with the cylinder certificate. An infrared detector calibrated on methane but protecting a propane area needs the manufacturer’s correction or calibration on the target gas.
- Response time: check that gas actually reaches the sensor through the weather protection and any calibration adapter; a slow T90 in the field is often a blocked or wrong accessory.
- Records: each test result belongs in the maintenance history, because proof testing the safety function depends on it.
Frequently asked questions
Can one detector cover both methane and hydrogen?
Not with infrared, which cannot see hydrogen. Catalytic detectors respond to both but have their own weaknesses, so hydrogen areas are usually covered with catalytic or dedicated hydrogen sensors alongside infrared detectors for hydrocarbons.
Is a portable gas monitor a substitute for fixed detection?
No. Portable monitors protect the person wearing them during entry and maintenance work. Fixed detection protects an area continuously and can start automatic actions. Most sites need both.